Sollatek AVR22.5KVA 22.5KVA Three Phase AVR

AVR22.5KVA
BrandSollatek ConditionNew Warranty IssuerManufacturer

 

Input


Input voltage 230/400V, -30%, +22%.
 Maximum Input Current 3x50 amps (at 100% load and maximum boost).
 Frequency Range 45Hz to 75Hz (i.e 50Hz –10%, +50%. or 60Hz –25%, +25%).
 Additional Voltage THD <0.2% at input (tested at 100% linear load), (No PWM methods used).
 Maximum Input THD Can withstand >10% THD from the supply.


Output


Output voltage 230/400V, +/- 4%.
 Maximum Output Current 3 x 33 amps.
 Maximum Output Power 22.5 kVA.
 Correction time 20 m sec (0 to 100% load).
 Additional Voltage THD <0.25% at output (tested at 100% linear load), (No PWM methods used).
 Crest Factor > 1: 3 permissible on load current (tested at 100% load).
 Synchronization Output synchronized to input.
 Permissible Overload 1000% for 100ms,
 150% for 4 minutes,
 110% for 10 minutes.
 Load Types Designed to run lighting, motors, battery chargers, communications equipment, offi ce equipment,
 SMPS, air- conditioners, compressors, industrial machines, medical equipment and others. Suitable
 for all domestic, commercial and industrial sites.


General
Isolation Transformer Connected at input. Delta primary plus earth, 4 wire. Star secondary plus earth, 5 wire. Inter-winding
 screen earthed at input.
Circuit Breakers Input and output circuit breakers to protect against overload and short circuit to both the AVR and
 the load.
 Voltage Protection AVS Automatic over and under voltage protection and adjustable re-connect delay, c/w fi ve status
 LED indicators. Protects load from extreme supply voltage and AVR malfunction.
 Output Alarm Visual indicator and volt-free contacts if AVR output fails for any reason.
 By-Pass Automatic by-pass to run load direct from utility power if AVR needs to be taken out of service for
 any reason. Status indicators for each phase.
 Technology All solid state (static) switching.
 Effi ciency AVR: >98%. Isolation transformer: >97% average, >95% worst case
 Control Microcontroller based control system provides self checks, system integrity monitoring and
 diagnostic indicators.
 Control Protection Internal surge arrestors and fi lters in control circuit protect against disturbances. Filtering algorithms
 and fault tolerant software protect against disturbances and false measurements.
 Power Connections Supply phases and earth. Load phases, neutral and earth.
 Surge Protection Heavy duty input and output surge arrestors to protect against extreme surges and lightning on the
 supply. Class II protection, 20kV, 1.2/50us, 45kA max surge current. Response time <20ns.
 With status indicators.
 RFI/EMI Filter AVR is equipped with RFI/EMI fi ltering for proper operation of the unit.
 Ambient Temperature Range -5 to +35ºC.
 Relative Humidity >95%, non-condensing.
 Environmental Protection IP20.
 Acoustic Noise < 45 dB (A).
 Expected Service Life > 25 years

130kg weight

Brand
Condition
  • New
Warranty Issuer
  • Manufacturer
Find similar

No reviews found